Need service? Call (888) 912-6684
Smart Filter Monitoringby Spray Booth Services
Back to the portal
Help center

How to read your chart

Every filter has a History page. Open it from a location page with the History button next to the filter. The chart shows how the filter has loaded up over time.

Example history chart, made-up data Readings rise from 0.10 to 0.27 in. w.c. over 18 days, into the amber Change soon band. Then the reading drops to 0.09, marked Filter changed, and starts rising slowly again. 0.000.100.200.300.40 Change soon 0.20 Past due 0.30 Filter changed Days (one point = the highest reading of a day) 1 2 3 4 5
Example only, with made-up readings. Your chart shows your own filter.
  1. The line is the filter's reading in inches of water column (in. w.c.). Each point is the highest reading of one day. A rising line means the filter is loading up with overspray and dust.
  2. The amber band starts at 0.20 in. w.c. In it, the filter shows Change soon: order filters and plan the change.
  3. The red band starts at 0.30 in. w.c. In it, the filter is Past due: change it as soon as you can.
  4. Filter changed marks where the reading dropped sharply to new-filter levels (a drop of 40% or more, to under 0.12). That is almost always a filter change. The Last filter change box above the chart uses the same rule.
  5. The latest reading is the last point on the right. New filters usually read about 0.08–0.10.

Other things on the History page

  • Last 7 / 14 / 30 / 90 change how many readings the chart shows.
  • Table view lists the same points as a table: date, reading and status.
  • Estimated time to Past due projects the recent trend. It's an estimate, not a guarantee.
  • Download report (PDF) and Download CSV save the readings for your records.

Each filter type's exact alert points are set up in your account, so a status can switch slightly before or after these lines. Questions? Call (888) 912-6684.